Morley-IAS by Honeywell - Manual Break-glass Call Point HM-MCP-GLASS-UL
Morley-IAS by Honeywell - Manual Break-glass Call Point HM-MCP-GLASS-UL
Manual Break-glass Call Point HM-MCP-GLASS-UL
Free
Fire Projects recommend the HM-MCP-GLASS-ULis an addressable manual break glass call point which, as a simple rotary decade, switch at the rear of the unit for addressing.
Fire Projects recommend the HM-MCP-GLASS-ULis an addressable manual break glass call point which, as a simple rotary decade, switch at the rear of the unit for addressing.
A specialist test key may be inserted into the bottom of the unit to lower the glass and release the micro-switch – enabling a complete functionality test.
The HM-MCP-GLASS- UL call point is designed to provide a manual alarm interface to Morley IAS’s fire alarm control panel. Installation efficiency and compliance with the latest standards are at the heart of the call point range.
• Innovative “Plug and Play” installation concept
• Analogue addressable communications
• Integral LED
Mechanical Specifications:
Size: • Semi-flush mounting: 89 x 93 x 27.5 (W x H x D)
• Surface mounting: 89 x 93 x 59.5 (W x H x D)
Weight: 110g (3.8 oz.)
IP Rating: IP24D
Operating Temperature: 0°C to 49°C (32°F – 120°F)
Relative Humidity: 10% - 93% non-condensing
Electrical Specifications:
Operating Voltage: 15V to 32Vdc max
Current Consumption: Quiescent (without isolator) 385μA Alarm Current: 7.8 mA
Turnkey solutions for Fire Detection, VESDA System, Fire Suppression, Fire Extinguishers, CCTV, Access Control and PA Systems for Industrial and Commercial market segments.