System Sensor Intelligent FAAST 8251F VESDA System

Fire Projects recommend Intelligent FAAST 8251F aspirating smoke detector that combines dual source (blue LED and infrared laser) optical smoke detection with fire alarm control panel connectivity via CLIP mode to provide high sensitivity to fire with intelligent reporting capabilities; all while providing enhanced immunity to nuisance particulate. As a result, FAAST can provide Early Warning and Very Early Warning Fire Detection while seamlessly integrating with an existing fire signalling circuit. 
 
Fire Project integrate intelligent FAAST detector  that can be wired to a new or pre-existing SLC for communications directly to a fire alarm control panel via CLIP mode without extra hardware. In CLIP mode, the 8251F FAAST will report back to the fire alarm control panel as an ACCLIMATE™ detector. By setting sensitivity levels in Pipe IQ equivalent to pre-alarm and alarm sensitivity settings in the panel, the fire alarm control panel will initiate pre-alarm (if pre-alarm exists in the panel) and alarm conditions based on feedback from the FAAST unit. Using CLIP, up to 99 units can populate one SLC. 
 
For initial system creation, FAAST’s design, configuration, and monitoring software, Pipe IQ, guides users through pipe layout. An installed device can be monitored through its integral display, from a computer connected to the device, or remotely through a web browser. When Internet-connected, FAAST can also e-mail status updates to appropriate personnel.
 
Select Fire Projects for new implementation of System Sensors - FAAST 8251 optical smoke detection is most effective way for very early smoke detection application for small to medium size datacenter, UPS room, medical facilities, and telecommunication facilities. We support our clients from Designing up to Commissioning up to AMC. We also provide AMC–Annual Maintenance Contracts for all types of Fire & security Systems. If you required new installation or AMC of VESDA system, contact Fire Projects today!
 
Schedule your appointment with Fire Projects on contact number +91 9409535460.
 
 
•  Approved for use in Class I, Division 2, Groups A, B, C, and D Hazardous Locations 
•  SLC connectivity via CLIP Protocol 
•  Up to 99 FAAST devices per loop 
•  Detection as precise as 0.00046 %/ft obscuration 
•  Five alarm levels and two sensitivity modes provide application flexibility 
•  Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement 
•  A single device protects up to 8,000 square feet 
•  Advanced detection algorithms reject common nuisance conditions 
•  Patented particle separator and field-replaceable filter remove contaminants from the system 
•  PipeIQ® software provides intuitive system layout, configuration, and monitoring all in one package 
•  Monitoring and configuration via Modbus/TCP protocol over Ethernet 
•  Fault indictors exhibit a broad spectrum of events 
•  Unique air flow pendulum graph verifies pipe network functionality 
•  Particulate graph displays subtle environmental changes for early problem indications 
Electrical Specifications:
  • External Supply Voltage: 18-30 VDC 
  • Remote Reset Time: External monitor must be pulled low for a minimum of 100 ms 
  • Power Reset:  1 sec. Avg. 
  • Operating Current:  500 mA @ 24 VDC 
  • Alarm: 650 mA – All relays active, all alarm levels displayed. Voltage @ 24 VDC 
  • Average SLC Current: 700uA 
  • SLC Voltage Range: 15 to 32 VDC 
  • Relay Contact Ratings: 3.0 A @ 30 VDC, 0.5 A @ 125 VAC 
Environmental Ratings:
  • Operating Temperature: 32°F (0°C) to 100°F (38°C) 
  • Sampled Air Temperature: -4°F (-20°C) to 140°F (60°C) 
  • Humidity Range: 10 to 95% (non-condensing) 
  • IP Rating: IP30
  •  Coverage Area: 8,000 sq. ft. (800 sq. m) 
  • Air Movement: 0-4,000 ft./min. (0-1,219 m/min.) 
Physical Specifications:
  • Height: 13.25 inches (33.7 cm) Width 13.0 inches (33 cm) 
  • Depth: 5.0 inches (12.7 cm) 
  • Cable Access: 4 1-inch (2.54 cm) cable entry holes on top and bottom of unit 
  • Wire Gauge: 12 AWG (2.05 mm) max. to 24 AWG (0.5 mm) min. 
  • Maximum Single Pipe Length: 262 ft. (80 m) 
  • Maximum Branched (2) Pipe Length:  165 ft. (50 m) each branch 
  • Maximum Air Inlet Holes: 40 holes 
  • Network Outside Pipe Diameter: 1.050 inches, IPS (25 mm)
  • Internal Pipe Diameter: 0.591 to 0.827 inches (15-21 mm) 
  • Sensitivity Range: 0.00046% Obs/ft to 6.25% Obs/ft (0.0015% Obs/m to 20.5% Obs/m) 
  • Relays: 6 form C, 3 AMP, programmable latching or non-latching 
  • Event Log: 18,000 events stored 
  • Communication Network:  Ethernet monitoring, 6 E-mail address alerts; Modbus/TCP 
  • Shipping Weight: 11.6 lbs. (5.3 kg), includes packing material