System Sensor Conventional FAAST 7100X VESDA System

The FAAST XS aspirating smoke detector installed by Fire Projects combine advanced particle separation with unique dual source optical smoke detection technology to provide highly sensitive Very Early Warning Fire Detection while providing enhanced immunity to false alarms. This technology enables FAAST XS to accurately detect incipient fire conditions as early as 60 minutes before a fire actually starts when set for Early Warning and Very Early Warning Fire Detection in applications ranging from mission critical to harsh and extreme environments. 
 
An installed FAAST XS device by Fire Projects can protect up to 5,000 sq. ft. (464 sq. m) in standard coverage type applications and can be monitored in several different ways, including: Serial or TCP Modbus, Ethernet over a LAN or a direct connection, or via FAAST XS’s onboard USB. When connected to a LAN, FAAST XS’s email server can provide email event notification to appropriate personnel. FAAST XS also communicates alarm and notifications via form C relays.
 
PipeIQ® is FAAST XS’s intuitive design, configuration, and monitoring software. The all-in-one program can be used to create a pipe network tailored to meet site specific Requirements, configure a FAAST XS device, and monitor an installed device - including live
trending and reading of historic reports.
 
Select Fire Projects for new implementation of System Sensors - FAAST 7100 combine advanced particle separation with unique dual source optical smoke detection technology to provide highly sensitive Very Early Warning Fire Detection while providing enhanced immunity to false alarms for small to medium size datacenter, UPS room, medical facilities, and telecommunication facilities. We support our clients from Designing up to Commissioning up to AMC. We also provide AMC–Annual Maintenance Contracts for all types of Fire & security Systems. If you required new installation or AMC of VESDA system, contact Fire Projects today!
 
Schedule your appointment with Fire Projects on contact number +91 9409535460.
 
•  Provides Very Early Warning Fire Detection, as precise as 0.00029%/ft obscuration
•  Three alarm levels and three sensitivity modes provide application flexibility
•  User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption
•  Ultrasonic flow sensing and chamber airflow monitoring for precise system health information
•  A single device covers up to 5,000 square feet (464 sq. m)
•  Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions
•  Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life of the fieldreplaceable filter
•  TCP and Serial modbus for easy integration with building management systems
•  Easy configuration via USB interface, no external power needed
•  Onboard Ethernet interface enables remote monitoring, configuration, web server and e-mail notifications
•  Multilingual LCD user interface allows for detailed device information and interaction such as: Active faults, precise airflow monitoring, reset of airflow baseline, test/reset/isolate, and more
•  Configurable air flow fault thresholds and verification period
•  Convenient wiring compartment
•  Status-at-a-glance provides immediate alarm, fault and airflow status
 
Electrical Specifications:
  • External Supply Voltage: 18-30 VDC
  • Remote Reset Time: External monitor must be pulled low for a minimum of 100 ms
  • Power Reset: 1 sec.
  • Operating Current: Fan High - 200mA, 4.8W; Fan Med - 151mA, 3.7W; Fan Low - 120mA, 2.1W
  • Alarm Current: Fan High - 230mA, 5.6W; Fan Med - 172mA, 4.2W; Fan Low - 142mA, 3.5W
  • Relay Contact Ratings: 3.0 A @ 30 VDC, 0.5 A @ 125 VAC 5 form C, 3 AMP, programmable latching or non-latching
Operating Specifications:
  • Operating Temperature: 32°F (0°C) to 100°F (38°C); Factory Tested to 131°F (55°C)
  • Sampled Air Temperature: -4°F (-20°C) to 140°F (60°C)
  • Humidity Range: 10 to 95% (non-condensing)
  • Sensitivity Range: 0.00029% Obs/ft to 6.25% Obs/ft (0.00095% Obs/m to 20.5% Obs/m)
  • IP Rating: IP30
  • Coverage Area: 5,000 sq.ft. (464 sq.m)
  • Air Movement: 0-4,000 ft./min. (0-1,219 m/min.)
Physical Specifications:
  • Height: 11.0 in (279mm)
  • Width: 9.0 in (229mm)
  • Depth: 6.25 in (159mm)
  • Cable Access: 3 1-inch (2.54 cm) cable entry holes on top, and back of the unit
  • Wire Gauge: 12 AWG (2.05 mm) max. to 24 AWG (0.5 mm) min.
  • Maximum Single Pipe Length: 180 ft. (54.9 m) *all designs must be verified within PipeIQ software
  • Total Aggregate Pipe Length: 300 ft. (91.5m) *all designs must be verified within PipeIQ software
  • Outside Pipe Diameter: 1.050 inches, IPS (25 mm)
  • Internal Pipe Diameter: 0.591 to 0.827 inches (15-21 mm)
  • Relays: 5 form C, 3 AMP, programmable latching or non-latching
Diagnostic Specifications:
  • Event Log: 18,000 events stored
  • Trend Data Log: Configurable sampling period 1 minute to 1 day.
  • Service Log 300 custom user entries
Networking Specifications:
  • Communication Network: Ethernet monitoring, 6 email address alerts, TCP and Serial Modbus
  • Network Services: DHCP, SMTP, HTTP, MODBUS/TCP, AutoIP, NetBIOS-NS, Serial MODBUS
  • Ethernet: 10/100Mbps, MDI-X
  • Modbus TCP or Serial: RS-485 Email 6 recipients, selectable notifications Webserver Read Configuration, Live View, Logs