Morley-IAS DXc Range Addressable Fire Alarm System

Fire Projects has expertise in SITC of  Morley-IAS DX Connexion panel, which is ideally suited for use in the protection of small to medium sized buildings. All in all, a compact, high performance, feature rich, economical fire alarm control panel designed to help both the installer and the end user.

The multi-protocol DX Connexion range of fire alarm control panels has been developed to be the most time efficient fire alrm control panel on the market to install. Fire Projects simply fix the control panel to the wall, connect the field wiring, power up and in as few as five button presses Fire Projects can have a compliant, working fire alarm system. The fire alarm control panel’s large graphical display provides a clear menu structure making the whole initial set-up process quick, clear and intuitive.
 
Fire Projects does complex configuration of fire alarm control panel either by control panel's mobile phone style keypad or by using the windows PC programming tool supplied with the fire alarm control panel. Morley-IAS fire alarm control panel allow text message for devices or zones to be imported from an excel speard sheet and it is flexible PC/Laptop programming tool saves time of programmer/system integrator or end user.
 
DXc range Morley-IAS addressable fire alarm control panels are available with large blue LCD display and support user to create 40 to 80 zone alarm with option to upload company logo.  DXc1 (1 Loop fire alarm control panel) , DXc2 (2 Loop fire alarm control panel) and DXc4 (4 Loop fire alarm control panel) addressable fire alarm control panel supports Apollo (Xplore, XP95 and Discovery), Hochiki (ESP) & System Sensor protocol devices.
 
Fire Projects suggest not to add more than 99 field detectors (Smoke detector, heat detector, multi detector) and 99 signaling devices (Sounder strobe, Hooter, manual call point, control module or monitor module) in each loop. In this DXc range there is one optional port for RS232 third party protocol interface. 
 
Selecting Fire Projects for new implementation of Morley- IAS DXc Range for entry level addressable fire alarm control panel that is cost effective way for small to medium size organization, offices and library. We support our clients from Designing up to Commissioning up to AMC. We also provide AMC–Annual Maintenance Contracts for all types of Fire & security Systems. If you required new installation or AMC of fire alarm system, contact Fire Projects today!
 
Schedule your appointment with Fire Projects on contact number +91 9409535460.
 
 
+ User Interface:
 
• Display: 6x40 character (240x64 pixels) blue liquid crystal display with backlight illumination
• Control Keys: Evacuate, Silence/Resound, Mute Buzzer, Extend Delay, System Reset, Show Alarm Zones
• Programmable: 2 independent programmable function
• Keys: keys and LED indicators
• Programming: 12 button alpha numeric key pad inc
• Keys: cancel and return keys plus 4 navigation keys and an OK key
• Indicators: Fire, Fault, Disablement, Test, Buzzer Muted, Delayed Mode, Sounders Silenced, sounders Disabled and Power. Also dedicated fault LEDs for System      Fault, Supply Fault and Earth Fault. 40 or 80 LED fire zone indicators optional.
 
+ Networking Features:
 
• Network up to 16 loops (16x1 loop panels, 8x2 loop panels, 4x4 loop panels or any mix up to max 16 loops)
• True peer-to-peer and fault tolerant network for high system reliability 
• BS5839 part 1 compliant network
 
+ Panel Features:
 
• Optional 40 or 80 zone alarm LEDs
• Easy 5 key-press set-up
• Large blue LCD display
• Supports USB upload/download
• Mobile phone style keypad and navigation keys
• Option to upload a company logo
 
+ Software Features:
 
• PC confi guration software (supplied with panel)
• 80 fi re zones (can be used with or without LEDs)
• 7 day timers
• Event logging
• Onboard diagnostics
• Class change function
• Coincidence and verification detection for false alarm management
• Sensitivity adjustment e.g. between day and night
• Input/output logic
 
+ Hardware Features:
 
• Battery backed real-time clock (2 & 4 loop)
• 2 independent sounder circuits
• 500mA multi-protocol loop driver
• 2 x onboard monitored inputs
• Optional programmable keyswitch for selected functions
• Plug-in connectors
 
Mechanical DXc1 DXc2 DXc4
Dimensions [mm] (HxWxD) 260 x390 x147 391.5 x390 x147 391.5 x390 x147
Weight(ExcludingBatteries) 4kg 4.5Kg 4.5kg
Colour RAL9002 -Greywhite RAL9002 -Greywhite RAL9002 -Greywhite
MountingHoles 3 3 3
Knockouts(20mm)

Top:25x

Bottom:2x

Top:25x

  Bottom:4x

Top:25x

  Bottom:4x

Operating Temperature 0°C to+40°C 0°C to+40°C 0°C to+40°C
RelativeHumidity 5%-95%non-condensing 5%-95%non-condensing 5%-95%non-condensing
  IP30(EN6059) IP30(EN6059) IP30(EN6059)